SIEMENS
6/62
Siemens CR 1 · 2015
6
Drive systems
SINAMICS S120 Cabinet Modules
Motor Modules in chassis format
■
Technical specifications
Line voltage 380 … 480 V 3 AC
DC link voltage 510 … 720 V DC
Motor Module in chassis format
Type
6SL3720-
1TE32-1AA3
6SL3720-
1TE32-6AA3
6SL3720-
1TE33-1AA3
6SL3720-
1TE33-8AA3
6SL3720-
1TE35-0AA3
6SL3720-
1TE36-1AA3
Type rating
• at
I
L
(50 Hz 400 V)
1)
kW
110
132
160
200
250
315
• at
I
H
(50 Hz 400 V)
1)
kW
90
110
132
160
200
250
• at
I
L
(60 Hz 460 V)
2)
hp
150
200
250
300
400
500
• at
I
H
(60 Hz 460 V)
2)
hp
150
200
200
250
350
350
Output current
• Rated current
I
rated A
A
210
260
310
380
490
605
• Base-load current
I
L
3)
A
205
250
302
370
477
590
• Base-load current
I
H
4)
A
178
233
277
340
438
460
• Maximum current
I
max A
A
307
375
453
555
715
885
DC link current
• Rated current
I
rated DC
when supplied from
-
Basic/Smart Line Module
A
252
312
372
456
588
726
-
Active Line Module
A
227
281
335
411
529
653
• Base-load current
I
L DC
3)
when supplied from
-
Basic/Smart Line Module
A
245
304
362
444
573
707
-
Active Line Module
A
221
273
326
400
515
636
• Base-load current
I
H DC
4)
when supplied from
-
Basic/Smart Line Module
A
224
277
331
405
523
646
-
Active Line Module
A
202
250
298
365
470
581
Power requirement
• 24 V DC aux. power supply
A
0.8
0.8
0.9
0.9
0.9
1.0
• 400 V AC
A
0.63
1.13
1.8
1.8
1.8
3.6
DC link capacitance
μ
F
4200
5200
6300
7800
9600
12600
Pulse frequency
5)
• Rated frequency
kHz
2
2
2
2
2
1.25
• Pulse frequency, max.
-
without current derating
Hz
2
2
2
2
2
1.25
-
with current derating
Hz
8
8
8
8
8
7.5
Power loss, max.
6)
• at 50 Hz 400 V
kW
1.86
2.5
2.96
3.67
4.28
5.84
• at 60 Hz 460 V
kW
1.94
2.6
3.1
3.8
4.5
6.3
Cooling air requirement
m
3
/s
0.17
0.23
0.36
0.36
0.36
0.78
Sound pressure level
L
pA
(1 m) at 50/60 Hz
dB
67
69
69
69
69
72
Motor connection
U2, V2, W2
M12 screws
M12 screws
M12 screws
M12 screws
M12 screws
M12 screws
• Conductor cross-section, max. (IEC)
mm
2
2 × 185
2 × 185
2 × 240
2 × 240
2 × 240
4 × 240
Cable length, max.
7)
• Shielded
m
300
300
300
300
300
300
• Unshielded
m
450
450
450
450
450
450
PE/GND connection
PE bar
PE bar
PE bar
PE bar
PE bar
PE bar
• Busbar cross-section
mm
2
600
600
600
600
600
600
• Conductor cross-section, max. (IEC)
mm
2
240
240
240
240
240
240
Degree of protection
IP20
IP20
IP20
IP20
IP20
IP20
Dimensions
• Width
mm
400
400
400
400
400
600
• Height
8)
mm
2200
2200
2200
2200
2200
2200
• Depth
mm
600
600
600
600
600
600
Weight, approx.
kg
145
145
286
286
286
490
Frame size
FX
FX
GX
GX
GX
HX
1)
Rated power of a typ. 6-pole standard induction motor based on
I
L
or
I
H
at
400 V 3 AC 50 Hz.
2)
Rated power of a typ. 6-pole standard induction motor based on
I
L
or
I
H
at
460 V 3 AC 60 Hz.
3)
The base-load current
I
L
is based on a duty cycle of 110 % for 60 s or
150 % for 10 s with a duty cycle duration of 300 s.
4)
The base-load current
I
H
is based on a duty cycle of 150 % for 60 s or
160 % for 10 s with a duty cycle duration of 300 s.
5)
For details of the relationship between pulse frequency and maximum
output current/output frequency,
see Catalog PM 21.
6)
The specified power loss represents the maximum value at 100 % capacity
utilization. The value is lower under normal operating conditions.
7)
Total of all motor cables. Longer cable lengths for specific configurations
are available on request.
See also SINAMICS Low Voltage Engineering
Manual.
8)
The cabinet height increases by 250 mm with IP21 degree of protection,
and by 400 mm with IP23 degree of protection.
© Siemens AG 2015