siemens sinamics dcm converter, siemens catalogues, siemens supplier, siemens distributor

Thousands of wholesale products available. Trusted Brands. Expertise. Support.

Save time and money! Contact us to buy now at +39 080.5367090 info@tecnicaindustriale.com

Siemens Sinamics Dcm Converter – page 52

SIEMENS
logo_siemens

Siemens catalogues

Click here for immediate price quote or call us at +39 080.5367090

SINAMICS DCM
DC Converter and Control Module
DC Converter
3/24
Siemens D 23.1 · 2014
3
■
Technical specifications
(continued)
SINAMICS DC MASTER converters for 480 V 3 AC, 15 to 210 A, four-quadrant operation
Note:
Detailed dimensional drawings in PDF and DXF format are
available on the Internet at
.
Data for single-phase connection
Type
6RA8013-
6FV62-0AA0
6RA8018-
6FV62-0AA0
6RA8025-
6FV62-0AA0
6RA8028-
6FV62-0AA0
6RA8031-
6FV62-0AA0
6RA8075-
6FV62-0AA0
Rated armature supply
voltage
1)
V
480 3 AC
(+15/-20 %)
480 3 AC
(+10/-20 %)
Rated armature input current
A
12
25
50
75
104
174
Rated supply voltage,
electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC;
I
n
= 1 A or
190 (-25 %) … 240 (+10 %) 2 AC;
I
n
= 2 A
Rated fan supply voltage
V
Self-ventilated
24 V DC internal
Rated fan current
A
Internal
supply
Cooling air requirement
m
3
/h
300
Sound pressure level
2)
dB (A)
52.4
Rated field supply voltage
1)
V
480 2 AC
(+10/-20 %)
Rated frequency
Hz
45 … 65
Rated DC voltage
1)
V
500
Rated DC current
A
15
30
60
90
125
210
Overload capability
x
×
I
n
1.8
Rated power
kW
6
15
30
45
63
105
Power loss at rated DC current
kW
0.13
0.19
0.30
0.34
0.43
0.72
Rated DC field voltage
1)
V
Max. 390
Rated DC field current
A
3
5
10
10
10
15
Normal ambient temperature
in operation
3)
°C
0 … +45
0 … +40
Storage and transport
temperature
°C
-40 … +70
Installation altitude above
sea level
3)
≤
1000 m for rated DC current
Dimensions
• Width
mm
268
• Height
mm
385
• Depth
mm
221
252
Weight, approx.
kg
11
14
15
Type
6RA8013-
6FV62-0AA0
6RA8018-
6FV62-0AA0
6RA8025-
6FV62-0AA0
6RA8028-
6FV62-0AA0
6RA8031-
6FV62-0AA0
Rated DC voltage
V
335
Rated DC current
A
10.5
21.0
42.0
63.0
87.5
1)
The armature/field supply voltage may be lower than the rated armature/
field voltage (set by parameter). A minimum input voltage of 50 V is permis-
sible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for
higher rated voltages. The output voltage is reduced accordingly. The
specified DC output voltage can be maintained up to an undervoltage of
5 % of the line supply voltage (rated armature/field supply voltage).
2)
Fan noise for a unit installed in an IP20 electrical cabinet (door closed,
50 Hz operation or operation at 24 V DC for units with an internal supply).
3)
For derating factors at higher temperatures and installation altitudes,
see page 3/8.
© Siemens AG 2014
1 - 2 - 3 - 4 - 5 - 6 - 7 - 8 - 9 - 10 - 11 - 12 - 13 - 14 - 15 - 16 - 17 - 18 - 19 - 20 - 21 - 22 - 23 - 24 - 25 - 26 - 27 - 28 - 29 - 30 - 31 - 32 - 33 - 34 - 35 - 36 - 37 - 38 - 39 - 40 - 41 - 42 - 43 - 44 - 45 - 46 - 47 - 48 - 49 - 50 - 51 - 52 - 53 - 54 - 55 - 56 - 57 - 58 - 59 - 60 - 61 - 62 - 63 - 64 - 65 - 66 - 67 - 68 - 69 - 70 - 71 - 72 - 73 - 74 - 75 - 76 - 77 - 78 - 79 - 80 - 81 - 82 - 83 - 84 - 85 - 86 - 87 - 88 - 89 - 90 - 91 - 92 - 93 - 94 - 95 - 96 - 97 - 98 - 99 - 100 - 101 - 102 - 103 - 104 - 105 - 106 - 107 - 108 - 109 - 110 - 111 - 112 - 113 - 114 - 115 - 116 - 117 - 118 - 119 - 120 - 121 - 122 - 123 - 124 - 125 - 126 - 127 - 128 - 129 - 130 - 131 - 132 - 133 - 134 - 135 - 136 - 137 - 138 - 139 - 140 - 141 - 142 - 143 - 144 - 145 - 146 - 147 - 148 - 149 - 150 - 151 - 152 - 153 - 154 - 155 - 156 - 157 - 158 - 159 - 160 - 161 - 162 - 163 - 164 - 165 - 166 - 167 - 168 - 169 - 170 - 171 - 172 - 173 - 174 - 175 - 176 - 177 - 178 - 179 - 180 - 181 - 182 - 183

Ask for a free quotation – We are at your disposal

Call us at +39 080.5367090 or send an email to info@tecnicaindustriale.com