siemens sinamics dcm converter, siemens catalogues, siemens supplier, siemens distributor

Thousands of wholesale products available. Trusted Brands. Expertise. Support.

Save time and money! Contact us to buy now at +39 080.5367090 info@tecnicaindustriale.com

Siemens Sinamics Dcm Converter – page 111

SIEMENS
logo_siemens

Siemens catalogues

Click here for immediate price quote or call us at +39 080.5367090

SINAMICS DCM
Accessories and supplementary components
SICROWBAR AC
4/25
Siemens D 23.1 · 2014
4
■
Technical specifications
General technical specifications
SICROWBAR AC
Degree of protection
IP00 acc. to EN 60529
Protection class
I according to EN 50178
Overvoltage category
III, corresponding to EN 60664
Dimensioning creepages and clearances
Pollution degree 2 acc. to EN 50178
Rated insulation voltage
(for installation altitudes up to 2000 m above sea level)
1)
725 V AC for rated supply voltages of 400 ... 725 V
1200 V AC for rated supply voltages of 850 ... 1150 V
Installation altitude
≤
2000 m above sea level
Permissible ambient temperature
• In operation
+5 ... +55 °C
• In storage
–40 ... +70 °C
Climate class
3K3 acc. to EN 60721-3-3
Fuse monitoring (microswitch at the fused disconnector,
1 changeover contact)
Flat connector 6.3 mm
×
0.8 mm
• Disconnector closed, all fuse links OK
1/2 closed, 1/4 opened
• Disconnector closed, one or several fuse links defective
1/4 closed, 1/2 opened
• Disconnector open
1/4 closed, 1/2 opened
• Maximum switching capacity
50 Hz 250 V AC, 3 A
30 V DC, 3 A
SICROWBAR AC
7VV3002-3CD20
7VV3002-3AD20
7VV3002-3BD20
7VV3002-3GD20
Max. permissible rated supply voltage
V
N
V
460
550
Nominal response voltage of BOD element
V
AN
V
1000
1200
1400
1600
Min. limit voltage of BOD element at 5 °C
V
RRM_05
V
864
1056
1248
1440
Max. limit voltage of BOD element at 55 °C
V
RRM_55
V
1166
1378
1590
1802
Max. permissible peak current,
I
max
A
200
1000
2000
Rated insulation voltage (the insulation voltage is determined by
the highest rated supply voltage of the relevant construction type)
V
ISO
V
550
Varistor voltage (breakdown voltage) at
T
A
= 25 °C, 1 mA
(data sheet value
×
2 for 2 series-connected varistors)
V
V
V
720
860
Max. energy (for 2 ms) at
T
A
= 85 °C
(data sheet value
×
2 for 2 series-connected varistors)
W
0
Ws
600
720
Energy that can be absorbed 100 times
(determined from the derating data)
W
2
Ws
350
419
Energy that can be absorbed 10000 times
(determined from the derating data)
W
4
Ws
42
50
Version
A
Dimensions
• Width
mm
265
• Height
mm
385
• Depth
mm
237
Weight, approx.
kg
7
1)
Installation altitudes above 2000 m on request.
© Siemens AG 2014
1 - 2 - 3 - 4 - 5 - 6 - 7 - 8 - 9 - 10 - 11 - 12 - 13 - 14 - 15 - 16 - 17 - 18 - 19 - 20 - 21 - 22 - 23 - 24 - 25 - 26 - 27 - 28 - 29 - 30 - 31 - 32 - 33 - 34 - 35 - 36 - 37 - 38 - 39 - 40 - 41 - 42 - 43 - 44 - 45 - 46 - 47 - 48 - 49 - 50 - 51 - 52 - 53 - 54 - 55 - 56 - 57 - 58 - 59 - 60 - 61 - 62 - 63 - 64 - 65 - 66 - 67 - 68 - 69 - 70 - 71 - 72 - 73 - 74 - 75 - 76 - 77 - 78 - 79 - 80 - 81 - 82 - 83 - 84 - 85 - 86 - 87 - 88 - 89 - 90 - 91 - 92 - 93 - 94 - 95 - 96 - 97 - 98 - 99 - 100 - 101 - 102 - 103 - 104 - 105 - 106 - 107 - 108 - 109 - 110 - 111 - 112 - 113 - 114 - 115 - 116 - 117 - 118 - 119 - 120 - 121 - 122 - 123 - 124 - 125 - 126 - 127 - 128 - 129 - 130 - 131 - 132 - 133 - 134 - 135 - 136 - 137 - 138 - 139 - 140 - 141 - 142 - 143 - 144 - 145 - 146 - 147 - 148 - 149 - 150 - 151 - 152 - 153 - 154 - 155 - 156 - 157 - 158 - 159 - 160 - 161 - 162 - 163 - 164 - 165 - 166 - 167 - 168 - 169 - 170 - 171 - 172 - 173 - 174 - 175 - 176 - 177 - 178 - 179 - 180 - 181 - 182 - 183

Ask for a free quotation – We are at your disposal

Call us at +39 080.5367090 or send an email to info@tecnicaindustriale.com