3/84
Siemens IK PI · 2015
■
Technical specifications
(continued)
PROFIBUS
Electrical networks (PROFIBUS PA)
Active field distributors
3
Active field splitter AFS
General data
Connection of field devices
• 1 fieldbus segment with max.
31 field devices
•
Operating environment up to Zone
2
oder 22; Class I Zone 2/ Division 2
• The max. current consumption of all
fieldbus components of the fieldbus
segment is 1 A
Degree of protection
IP66
Voltages, currents, potentials
Power supply
Via bus, no auxiliary power necessary
Rated supply voltage,
permissible range
16 ... 32 V DC
Reverse polarity protection
(together with FDC 157)
Yes
Overvoltage protection
No
Current consumption at idle
54 mA
Power loss
Min. 864 mW; max. 2.13 W
Output current for supplying all field
devices of the fieldbus segment
(for dimensioning the device
configuration)
1 A
Grounding
Direct, via connecting bar
Connections, interfaces
Main lines to the FDC 157 couplers
Number of connections
2
Automatic bus terminator
No
Maximum permissible continuous
main line current
1 A
Y-connectors for
fieldbus line segment
Number of connections
1 or 2 (with center feed)
Interfaces
PROFIBUS PA and
FOUNDATION Fieldbus H1
Short-circuit proof
(together with FDC 157)
Yes
Intrinsically-safe acc. to FISCO
No
Current I
max
on Y (limited by FDC 157)
1 A
Debounce logic
No
Continuous output voltage
Max. 32 V
Current output to field devices
Max. 1 A
Status, interrupts, diagnostics
Status indicator
Yes
Diagnostics function
Yes
Diagnostics LED
Yes
Interrupts
No
Climatic conditions
Permissible operating temperature
-40 ... +70 °C
Permissible storage/transport
temperature
-40 ... +85 °C
Relative humidity during operation
Max. 95 %
Approvals for potentially explosive
atmospheres
• Gas
Zone 2
• Dust
Zone 22
Dimensions and weight
Dimensions (W x H x D)
in mm (without fittings)
220 x 120 x 83
Weight
2 000 g
■
Ordering data
Article No.
Active field distributor (AFD)
For integration of standard-
compliant PA or FF field devices
• AFD4 with 4 short-circuit-proof
spur line connections
for 1 field device each
6ES7157-0AG81-0XA0
• AFD8 with 8 short-circuit-proof
spur line connections
for 1 field device each
6ES7157-0AG82-0XA0
Active Field Distributor
AFDiS (Active Field Distributor
intrinsically safe)
with 6 short-circuit-proof spur line
connections for the integration of
standard-compliant intrinsically-
safe PA or FF field devices
6ES7157-0AG83-0XA0
Active field splitter (AFS)
for the interconnection of a bus line
segment with the active coupler
of a PA or FF router with redundant
coupler pair
6ES7157-0AG80-0XA0
Accessories
Sealing plugs
for unused connections on AFS,
AFD and AFDiS (10 units)
6ES7157-0AG80-1XA1
© Siemens AG 2014
1 - 2 - 3 - 4 - 5 - 6 - 7 - 8 - 9 - 10 - 11 - 12 - 13 - 14 - 15 - 16 - 17 - 18 - 19 - 20 - 21 - 22 - 23 - 24 - 25 - 26 - 27 - 28 - 29 - 30 - 31 - 32 - 33 - 34 - 35 - 36 - 37 - 38 - 39 - 40 - 41 - 42 - 43 - 44 - 45 - 46 - 47 - 48 - 49 - 50 - 51 - 52 - 53 - 54 - 55 - 56 - 57 - 58 - 59 - 60 - 61 - 62 - 63 - 64 - 65 - 66 - 67 - 68 - 69 - 70 - 71 - 72 - 73 - 74 - 75 - 76 - 77 - 78 - 79 - 80 - 81 - 82 - 83 - 84 - 85 - 86 - 87 - 88 - 89 - 90 - 91 - 92 - 93 - 94 - 95 - 96 - 97 - 98 - 99 - 100 - 101 - 102 - 103 - 104 - 105 - 106 - 107 - 108 - 109 - 110 - 111 - 112 - 113 - 114 - 115 - 116 - 117 - 118 - 119 - 120 - 121 - 122 - 123 - 124 - 125 - 126 - 127 - 128 - 129 - 130 - 131 - 132 - 133 - 134 - 135 - 136 - 137 - 138 - 139 - 140 - 141 - 142 - 143 - 144 - 145 - 146 - 147 - 148 - 149