Overview
(continued)
PROFIBUS
Electrical networks (PROFIBUS PA)
Active field distributors
3
Active field distributor AFDiS
Active field distributor AFDiS
The active field distributor AFDiS (Active Field Distributor intrin-
sically Safe) can be operated in environments in accordance
with Ex zone 1/21 and 2/22. It can integrate up to 6 intrinsically-
safe PA or FF field devices into a fieldbus segment (line/ring) via
its intrinsically-safe, short-circuit-proof spur line connections.
Instead of the spur line, it is also possible to use a subsegment
for 3 to 4 devices with a max. length of 500 m at connection S1
of the AFDiS. The spur lines with type of protection Ex [ia] as well
as the subsegment can be routed into Zone 0/20.
Up to 5 field distributors AFDiS with a total of up to 31 field
devices can be operated in a fieldbus segment. The limitation to
5 field distributors is also mandatory for mixed operation of AFD
and AFDiS.
The number of field devices per segment additionally depends
on the current consumption of the devices. A current of 1 A is
available for all field devices of the segment.
With the integrated repeater function, the AFDiS has the
following advantages compared to the AFD:
•
Spur line lengths are independent of the total number of spur
lines in the bus segment
•
Spur line lengths need not be be taken into account when
determining the total length of the bus segment
Under the following conditions, an AFDiS in a ring segment can
be replaced during operation without failure of the segment:
Installation in Zone 2/22 or in a non-hazardous area.
For compliance with IP66 protection, it is necessary to protect
unused spur line connections by plugs.
Active field splitter AFS
The active field splitter (AFS) connects a PA or FF line segment
with a redundant coupler pair of a PA or FF router. The AFS inter-
connects the line segment with the respective active coupler.
The PA or FF line segment can be connected to the AFS via one
or two (center feed) identical Y-connectors out of a total of 4.
For the center feed, the line segment is connected via the two
Y-connectors (bus termination switch on both FDC 157 couplers
set to "OFF").
For compliance with IP66 protection, it is necessary to protect
unused connections by plugs.
Bus
terminating
resistor 100 Ω
Subsegment max. 500 m
PA link
Ex Zone 1
Ex Zone 0
PROFIBUS DP
G_PCS7_XX_00285
AFDiS
AFDiS
AFDiS
© Siemens AG 2014
1 - 2 - 3 - 4 - 5 - 6 - 7 - 8 - 9 - 10 - 11 - 12 - 13 - 14 - 15 - 16 - 17 - 18 - 19 - 20 - 21 - 22 - 23 - 24 - 25 - 26 - 27 - 28 - 29 - 30 - 31 - 32 - 33 - 34 - 35 - 36 - 37 - 38 - 39 - 40 - 41 - 42 - 43 - 44 - 45 - 46 - 47 - 48 - 49 - 50 - 51 - 52 - 53 - 54 - 55 - 56 - 57 - 58 - 59 - 60 - 61 - 62 - 63 - 64 - 65 - 66 - 67 - 68 - 69 - 70 - 71 - 72 - 73 - 74 - 75 - 76 - 77 - 78 - 79 - 80 - 81 - 82 - 83 - 84 - 85 - 86 - 87 - 88 - 89 - 90 - 91 - 92 - 93 - 94 - 95 - 96 - 97 - 98 - 99 - 100 - 101 - 102 - 103 - 104 - 105 - 106 - 107 - 108 - 109 - 110 - 111 - 112 - 113 - 114 - 115 - 116 - 117 - 118 - 119 - 120 - 121 - 122 - 123 - 124 - 125 - 126 - 127 - 128 - 129 - 130 - 131 - 132 - 133 - 134 - 135 - 136 - 137 - 138 - 139 - 140 - 141 - 142 - 143 - 144 - 145 - 146 - 147 - 148 - 149