3/83
Siemens IK PI · 2015
3
■
Technical specifications
(continued)
PROFIBUS
Electrical networks (PROFIBUS PA)
Active field distributors
Active field distributor AFDiS
General data
Connection of field devices
• Standard-compliant field devices
for PROFIBUS PA or FOUNDATION
Fieldbus H1
• Max. 6 per AFDiS
• Max. 31 per fieldbus segment
•
Operating environment up to Zone
1
oder 21; Class I Zone 1
• The max. current consumption of all
fieldbus components of the fieldbus
segment is 1 A
Degree of protection
IP66
Voltages, currents, potentials
Power supply
Via bus, no auxiliary power necessary
Rated supply voltage,
permissible range
16 ... 32 V DC
Reverse polarity protection
(together with FDC 157)
Yes; up to 1 A
Overvoltage protection
No
Current consumption
• At 28 V input voltage
64 mA + (0.838 x aggregate current
of all field devices)
• At 24 V input voltage
67 mA + (1.008 x aggregate current
of all field devices)
• At 20 V input voltage
74 mA + (1.246 x aggregate current
of all field devices)
Power loss
Min. 1.4 W; max. 5.9 W
Grounding
Direct, via connecting bar
Electrical isolation between
main line and spur lines
Yes
Test voltage
2550 V DC, 2 s
Connections, interfaces
Main line
Number of connections
2
Interfaces
PROFIBUS PA and
FOUNDATION Fieldbus H1
Automatic bus terminator
Yes
Spur cables
Number of connections
6
Short-circuit-proof
Yes
Intrinsically-safe acc. to FISCO
Yes
Current I
max
• on spur line S1
60 mA
• on spur line S2 to S6
40 mA
• in total for all field devices
180 mA
Short-circuit current (test current)
5 mA
Debounce logic
Yes
No-load voltage
Max. 15.3 V
Current output to field devices
Max. 260 mA
Status, interrupts, diagnostics
Status indicator
Yes
Diagnostics function
Yes
Diagnostics LED
Yes
Interrupts
No
Climatic conditions
Permissible operating temperature
-40 ... +70 °C
Permissible storage/transport
temperature
-40 ... +85 °C
Relative humidity during operation
Max. 95 %
Approvals for potentially explosive
atmospheres
• Gas
Zone 1 and Zone 2
• Dust
Zone 21 and Zone 22
Dimensions and weight
Dimensions (W x H x D) in mm
380 x 85 x 170
Weight
4 500 g
Active field distributor AFDiS
© Siemens AG 2014
1 - 2 - 3 - 4 - 5 - 6 - 7 - 8 - 9 - 10 - 11 - 12 - 13 - 14 - 15 - 16 - 17 - 18 - 19 - 20 - 21 - 22 - 23 - 24 - 25 - 26 - 27 - 28 - 29 - 30 - 31 - 32 - 33 - 34 - 35 - 36 - 37 - 38 - 39 - 40 - 41 - 42 - 43 - 44 - 45 - 46 - 47 - 48 - 49 - 50 - 51 - 52 - 53 - 54 - 55 - 56 - 57 - 58 - 59 - 60 - 61 - 62 - 63 - 64 - 65 - 66 - 67 - 68 - 69 - 70 - 71 - 72 - 73 - 74 - 75 - 76 - 77 - 78 - 79 - 80 - 81 - 82 - 83 - 84 - 85 - 86 - 87 - 88 - 89 - 90 - 91 - 92 - 93 - 94 - 95 - 96 - 97 - 98 - 99 - 100 - 101 - 102 - 103 - 104 - 105 - 106 - 107 - 108 - 109 - 110 - 111 - 112 - 113 - 114 - 115 - 116 - 117 - 118 - 119 - 120 - 121 - 122 - 123 - 124 - 125 - 126 - 127 - 128 - 129 - 130 - 131 - 132 - 133 - 134 - 135 - 136 - 137 - 138 - 139 - 140 - 141 - 142 - 143 - 144 - 145 - 146 - 147 - 148 - 149