siemens sinamics g130 g150, siemens catalogues, siemens supplier, siemens distributor

Thousands of wholesale products available. Trusted Brands. Expertise. Support.

Save time and money! Contact us to buy now at +39 080.5367090 info@tecnicaindustriale.com

Siemens Sinamics G130 G150 – page 115

SIEMENS
logo_siemens

Siemens catalogues

Click here for immediate price quote or call us at +39 080.5367090

3/71
Siemens D 11 · 2015
3
SINAMICS G130
Drive converter chassis units
Supplementary system components > VSM10 Voltage Sensing Module
■
Overview
The VSM10 Voltage Sensing Module enables the line or motor
voltage characteristic to be measured precisely. The phase dif-
ferential voltage can be measured, either grounded (in the deliv-
ery state with jumper plugged in) or isolated.
In addition, the VSM10 Voltage Sensing Module is used to
connect to rotating synchronous motors – or for a "quick flying
restart" of rotating induction motors.
■
Design
The VSM10 Voltage Sensing Module has the following inter-
faces:
•
1 connection for direct voltage sensing up to 690 V
•
1 connection for voltage sensing using voltage transformers,
maximum voltage 100 V
•
1 temperature sensor input (KTY84-130 or PTC)
•
1 DRIVE-CLiQ socket
•
1 connection for the electronics power supply via the 24 V DC
supply connector
•
1 plug-in jumper for either grounded (delivery state) or
isolated measurement
•
1 PE connection
The status of the VSM10 Voltage Sensing Module is indicated by
a two-color LED.
The VSM10 Voltage Sensing Module can be snapped onto a
TH 35 mounting rail according to EN 60715 (IEC 60715).
■
Selection and ordering data
For the SINAMICS G150, the VSM10 Voltage Sensing Module
can be ordered as an option with order code
K51
to implement
the flying restart function.
■
Technical specifications
Description
Article No.
VSM10 Voltage Sensing Module
Without DRIVE-CLiQ cable
6SL3053-0AA00-3AA1
VSM10 Voltage Sensing Module
6SL3053-0AA00-3AA1
Power requirement, max.
at 24 V DC
0.2 A
• Conductor cross section, max.
2.5 mm
2
Power loss
< 10 W
Line voltage detection
• Insulation resistance
neutral point - ground when the jumper is
not inserted
> 10 M
Ω
• Input resistance
-
Terminal X521
> 362 k
Ω
/phase
-
Terminal X522
> 2.5 M
Ω
/phase
2 analog inputs
(reserved for monitoring an Active Interface
Module in chassis format)
• Internal resistance (between differential in-
puts)
Approx. 100 k
Ω
• Resolution
12-bit
PE connection
On housing with M4 screw
Dimensions
• Width
50 mm
• Height
150 mm
• Depth
111 mm
Weight, approx.
0.9 kg
© Siemens AG 2015
1 - 2 - 3 - 4 - 5 - 6 - 7 - 8 - 9 - 10 - 11 - 12 - 13 - 14 - 15 - 16 - 17 - 18 - 19 - 20 - 21 - 22 - 23 - 24 - 25 - 26 - 27 - 28 - 29 - 30 - 31 - 32 - 33 - 34 - 35 - 36 - 37 - 38 - 39 - 40 - 41 - 42 - 43 - 44 - 45 - 46 - 47 - 48 - 49 - 50 - 51 - 52 - 53 - 54 - 55 - 56 - 57 - 58 - 59 - 60 - 61 - 62 - 63 - 64 - 65 - 66 - 67 - 68 - 69 - 70 - 71 - 72 - 73 - 74 - 75 - 76 - 77 - 78 - 79 - 80 - 81 - 82 - 83 - 84 - 85 - 86 - 87 - 88 - 89 - 90 - 91 - 92 - 93 - 94 - 95 - 96 - 97 - 98 - 99 - 100 - 101 - 102 - 103 - 104 - 105 - 106 - 107 - 108 - 109 - 110 - 111 - 112 - 113 - 114 - 115 - 116 - 117 - 118 - 119 - 120 - 121 - 122 - 123 - 124 - 125 - 126 - 127 - 128 - 129 - 130 - 131 - 132 - 133 - 134 - 135 - 136 - 137 - 138 - 139 - 140 - 141 - 142 - 143 - 144 - 145 - 146 - 147 - 148 - 149 - 150 - 151 - 152 - 153 - 154 - 155 - 156 - 157 - 158 - 159 - 160 - 161 - 162 - 163 - 164 - 165 - 166 - 167 - 168 - 169 - 170 - 171 - 172 - 173 - 174 - 175 - 176 - 177 - 178 - 179 - 180 - 181 - 182 - 183 - 184 - 185 - 186 - 187 - 188 - 189 - 190 - 191 - 192 - 193 - 194 - 195 - 196 - 197 - 198 - 199 - 200 - 201 - 202 - 203 - 204 - 205 - 206 - 207 - 208 - 209 - 210 - 211