SIEMENS
1-6
2015
Low Voltage AC Motors Selection and Pricing Guide
Introduction
General capabilities for use with adjustable speed drives
The SIMOTICS product line offer a variable speed drive
operation for both severe duty and general purpose
applications as well as for explosion proof classifications
areas. In general, our standard line design is suitable for
inverter or vector applications where a maximum of 4:1
constant torque is required, motors with copper rotor
design GP100, SD100 and SD100 IEEE841 can provide
up to 10:1 Constant torque and our Severe Duty line in
four pole motors frame sizes 143-365 is suitable for up
to 20:1 constant torque.
1)
*4:1 C.T. for std fan, 6:1 or 10: C.T. M05 option code.
2)
Marking of Zone 2 as option (M22 – additional nameplate).
3)
Available as an option (L29 +L81 +M25 -Seal leads, Inpro®Seal, additional marking plate).
Frame
Constant
Torque
Variable
Torque
Class I, Div. 2 Gr. A, B, C or D
2)
Class I, Zone 2, Groups IIC
3)
Class II, Div. 2 Gr. F & G
Temperature code
Max. Temperature
Temperature code
Max. Temperature
143T - 145T
20:1
20:1
T4 (275ºF)
T4A (120ºF)
182T -
184T
20:1
20:1
T3A (180ºF)
T4A (120ºF)
213T - 215T
20:1
20:1
T3A (180ºF)
T4A (120ºF)
254T - 256T
20:1
20:1
T3A (180ºF)
T4A (120ºF)
324T - 326T
20:1
20:1
T3A (180ºF)
T4A (120ºF)
364T - 365T
20:1
20:1
T3A (180ºF)
T4A (120ºF)
404T - 405T
1)
10:1
20:1
T3A (180ºF)
T4A (120ºF)
444T - 445T
1)
10:1
20:1
T3 (200ºF)
T4A (120ºF)
447T
1)
6:1
20:1
T3 (200ºF)
T4A (120ºF)
449T
4:1
20:1
T2D (215ºF)
T4A (120ºF)
S449
4:1
20:1
T2D (215ºF)
T4A (120ºF)
Frame
Constant
Torque
Variable
Torque
XP100
Class I, Div. 1 Gr. C and D
Class I, Div 2, Groups E, F
and G
Class I, Div. 1 Gr. D
Temperature code
Max. Temperature
Temperature code
Max. Temperature
Constant
Torque
Variable
Torque
143T - 145T
4:1
20:1
T3C (160ºF)
T2D (215ºF)
4:1
100:1
182T - 184T
4:1
20:1
T3C (160ºF)
T2D (215ºF)
4:1
100:1
213T - 215T
4:1
20:1
T3C (160ºF)
T2D (215ºF)
4:1
100:1
254T - 256T
4:1
20:1
T3C (160ºF)
T2D (215ºF)
4:1
100:1
324T - 326T
4:1
20:1
T3C (160ºF)
T2D (215ºF)
4:1
100:1
364T - 365T
1)
6:1
20:1
T3C (160ºF)
T2D (215ºF)
4:1
100:1
404T - 405T
1)
6:1
20:1
T3C (160ºF)
T2D (215ºF)
4:1
100:1
444T - 445T
1)
6:1
20:1
T3C (160ºF)
T2D (215ºF)
4:1
100:1
447T
1)
4:1
20:1
T3C (160ºF)
T2D (215ºF)
4:1
100:1
Variable speed drive operation
Severe Duty Motors: SD100, SD661, SD841
Explosion Proof Motors: XP100, XP100 ID1