SIEMENS
3/19
Siemens D 15.1 · 2017
Technical Data
SINAMICS PERFECT HARMONY GH180, article number 6SR4...
3
■
Technical data
(continued)
SINAMICS PERFECT HARMONY GH180
air-cooled drive version
6SR4102-
2.E42-2..0
6SR4102-
2.E42-5..0
6SR4102-
2.E43-0..0
6SR4102-
2.F43-0..0
6SR4102-
2.F43-5..0
Motor voltage 6.6 kV
Max. output voltage
kV
6.6
6.6
6.6
6.6
6.6
Type rating
kVA
1980
2200
2285
2640
2970
Shaft output
1)
kW
1679
1865
1939
2238
2521
hp
2250
2500
2600
3000
3380
Typical motor current
1)
A
173
192
200
231
260
Power cell current
A
200
200
200
260
260
Number of cells
15
15
15
15
15
Aluminum transformer available
Yes
Yes
Yes
On request
No
Power loss of drive system
• with copper transformer
kW
< 60
< 66
< 68
< 79
< 89
• with aluminum transformer
kW
< 68
< 75
< 78
–
–
Efficiency
P
out
/
P
in
2)
of drive system
• with copper transformer
%
96.5
96.5
96.5
96.5
96.5
• with aluminum transformer
%
96
96
96
–
–
Auxiliary supply
• Single-phase w/o options
3)
kVA
< 1.5
< 1.5
< 1.5
< 1.5
< 1.5
• Single-phase w/ all options
3)
kVA
< 3
< 3
< 3
< 3
< 3
• Three-phase w/o CPT
4)
kVA
< 8
< 8
< 8
< 8
< 8
• Three-phase w/ CPT and all
options
4)
kVA
< 11
< 11
< 11
< 11
< 11
Cooling medium flow rate
m
3
/s
6.4
6.4
6.4
6.4
6.4
CFM
13600
13600
13600
13600
13600
Sound pressure level
L
pA
(1 m)
dB (A)
80
80
80
80
80
Power cabling cross-sections
• Cable cross-sections,
line-side, max. connectable per
phase
5)
AWG/MCM
(NEC, CEC)
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
mm
2
(DIN VDE)
2 x 240
2 x 240
2 x 240
2 x 240
2 x 240
• Cable cross-sections,
motor-side, max. connectable
per phase
5)
AWG/MCM
(NEC, CEC)
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
mm
2
(DIN VDE)
2 x 240
2 x 240
2 x 240
2 x 240
2 x 240
• PE connection,
max. connection cross-section
at enclosure
5)
AWG/MCM
(NEC, CEC)
2/0 AWG
2/0 AWG
2/0 AWG
2/0 AWG
2/0 AWG
mm
2
(DIN VDE)
70
70
70
70
70
Degree of protection
NEMA1/IP21
NEMA1/IP21
NEMA1/IP21
NEMA1/IP21
NEMA1/IP21
Drive dimensions (transformer cabinet and cell cabinet)
• Width
mm
4165
4165
4165
4165
4165
in
164
164
164
164
164
• Height (incl. blowers)
mm
2990
2990
2990
2990
2990
in
117.5
117.5
117.5
117.5
117.5
• Depth
mm
1250
1250
1250
1250
1250
in
49
49
49
49
49
• Schematic drawing
6)
B
B
B
B
B
Drive weight (transformer cabinet and cell cabinet)
• Weight, approx.
kg
7200
7400
7800
7800
8100
lb
15870
16310
17200
17200
17860
1)
The specifications for the typical motor current and the power data in kW and hp are approximate values only; these have been calculated for operation with
induction motors and for a typical power factor cos
and motor efficiency. Both approximate values have to be adapted to the motor that is actually used.
2)
Values at 100 % of rated speed and torque; includes drive and input transformer.
3)
120/240 V AC for NXGpro control
- 6SR4... drives derive single-phase control power from a built-in CPT as standard.
- For 6SR4... drives, customers can directly connect single-phase control power as an option (
K68
).
- CPT is an option in other systems.
4)
Includes cooling blowers/pumps; data refers to the largest unit.
5)
Maximum installable size per phase.
6)
Please refer to page 3/3
for schematic drawings.
© Siemens AG 2017