Technical specifications
SINAMICS G110 standard inverters
0.12 kW to 3 kW (0.16 hp to 4 hp)
Controlled Power Modules
Overview of SINAMICS G110 components and PDS categories
Electromagnetic compatibility
Observing the installation guidelines specific to the product will
ensure electromagnetic compliance.
The table below lists the measured results for emissions of and
immunity to interference for the SINAMICS G110 inverters.
The inverters were installed according to the guidelines with
shielded motor cables and shielded control cables.
Environment 1
(Residential,
commercial)
Category C1
Unfiltered devices and external filter class B with low leakage currents (shielded motor cable up to 5 m (16.41 ft))
Environment 2
(Industry)
Category C2
All devices with integrated filter
(shielded motor cable up to 5 m (16.41 ft))
or
All devices with integrated filter
(frame size FSA: up to 10 m (32.81 ft);
Frame sizes FSB and FSC: shielded motor cable
up to 25 m (82.03 ft)) + warning
or
All devices with integrated filter plus external filter,
class B (shielded motor cable up to 25 m (82.03 ft))
Category C2
All devices with integrated filter
(shielded motor cable up to 5 m (16.41 ft))
or
All devices with integrated filter
(frame size FSA: up to 10 m (32.81 ft);
Frame sizes FSB and FSC: shielded motor cable
up to 25 m (82.03 ft))
or
All devices with integrated filter plus external filter,
class B (shielded motor cable up to 25 m (82.03 ft))
Note: When devices with an integrated filter and a max.
motor cable length of 5 m (16.41 ft) or external class B
filters are used, this exceeds the requirements of
EN 61800-3 by a considerable margin!
Category C3
All devices with integrated filter (frame size FSA: up to 10 m (32.81 ft); frame sizes FSB and FSC:
shielded motor cable up to 25 m (82.03 ft))
or
All devices with integrated filter plus external filter, class B (shielded motor cable up to 25 m (82.03 ft))
A warning note is required.
Note: When devices with an integrated filter and external class B filters are used, this exceeds the
requirements of EN 61800-3 by a considerable margin!
Category C4
Does not apply to SINAMICS G110
EMC phenomenon
Standard/test
Relevant criteria
Limit value
Noise emissions
EN 61800-3
(environment 1)
Conducted via mains cable
150 kHz ... 30 MHz
Unfiltered devices: not tested
All devices with integrated/external filter:
Depending on the filter type and intended PDS
installation:
Category C1:
The limit value corresponds to EN 55011, class B.
Category C2:
The limit value corresponds to EN 55011, class A,
group 1
Further, all drive units with an integrated/external filter
fulfill the limit value for category C3 installations.
The limit value corresponds to EN 55011, class A,
group 2.
Emitted by the drive
30 MHz ... 1 GHz
All devices
The limit value corresponds to EN 55011, class A, group 1
ESD immunity
EN 61000-4-2
ESD by air discharge
Test level 3
8 kV
ESD by contact discharge
Test level 3
6 kV
Electrical fields immunity
EN 61000-4-3
Electrical field applied to
unit
Test level 3
80 MHz ... 1 GHz
10 V/m
Burst interference immunity
EN
61000-4-4
Applied to all cable
terminations
Test level 4
4 kV
Surge immunity
EN 61000-4-5
Applied to mains cables
Test level 3
2 kV
Immunity to RFI emissions, conducted
EN 61000-4-6
Applied to mains, motor and
control cables
Test level 3
0.15 MHz ... 80 MHz
80 % AM (1 kHz)
10 V