SIEMENS
5/15
Siemens D 31 · 2015
5
■
Technical specifications
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
SINAMICS G120 standard inverters
Note:
The EMC product standard EN 61800-3 does not apply directly
to a frequency inverter but to a PDS (Power Drive System), which
comprises the complete circuitry, motor and cables in addition
to the inverter. The frequency inverters on their own do not
generally require identification according to the EMC Directive.
Compliance with standards
CE marking
The SINAMICS G120 inverters meet the requirements of the
Low-Voltage Directive 2006/95/EC.
Low-Voltage Directive
The inverters comply with the following standards listed in the
official journal of the EU:
• EN 60204
Safety of machinery, electrical equipment of machines
• EN 61800-5-1
Electrical power drive systems with variable speed – Part 5-1:
Requirements regarding safety – electrical, thermal, and
energy requirements
UL listing
Inverter devices in UL category NMMS certified to UL and cUL,
in compliance with UL508C. UL list numbers E121068 and
E192450. This applies to all PM230 Power Modules degree of
protection IP20 (cUL only with frame sizes FSA to FSC), PM240,
PM240-2 and PM250 Power Modules with integrated line filter
class A.
For use in environments with pollution degree 2.
See also
www.ul.com
Machinery Directive
The inverters are suitable for installation in machines.
Compliance with the Machinery Directive 2006/42/EC requires a
separate certificate of conformity. This must be provided by the
plant construction company or the organization marketing the
machine.
1)
Applies to all PM230 Power Modules degree of protection IP20
(cUL only with frame sizes FSA to FSC), PM240-2, PM240 and PM250
Power Modules with integrated line filter class A.
2)
Non-filtered devices are designed for operation on IT systems or in con-
junction with an RCD. The customer must provide suitable RI suppression
equipment to ensure that these devices comply with the limits defined for
Category C3 or C2.
3)
With shielded motor cable up to 25 m (82 ft).
General technical specifications
Certification for fail-safe versions
Applies to Control Units of the
CU240E-2 and CU250S-2 Series.
The values comprise the Control Unit
and Power Module.
• According to IEC 61508
SIL 2
• According to EN ISO 13849-1
PL d and Category 3
Standards
Compliance with standards
UL
1)
, cUL
1)
, CE, C-Tick, SEMI F-47
CE marking
According to Low-Voltage Directive
2006/95/EC
EMC Directive
According to EN 61800-3
EMC Directive
according to EN 61800-3
Interference immunity
PM230 Power Modules
with degree of protection IP20
PM240-2 Power Modules
PM240 Power Modules
PM250 Power Modules
The Power Modules are tested with
the interference immunity require-
ments for environments according
to Category C3
Interference emissions
PM230 Power Modules
with degree of protection IP20
• Frame sizes FSA to FSF
without integrated line filter
2)
• Frame sizes FSA to FSF
with integrated line filter class A
Observance of the limit values
according to Category C3 and C2
3)
• Frame sizes FSA to FSF
without integrated line filter with
optional line filter class B
Observance of the limit values
-
for low-frequency harmonic effects
and conducted interferences
according to Category C1
-
for field-conducted radiated
interferences according to
Category C2
3)
PM240-2 Power Modules
• Frame sizes FSA to FSC
without integrated line filter
2)
• Frame sizes FSA to FSC
with integrated line filter class A
Observance of the limit values
-
according to Category C3
-
for conducted interferences and
field-conducted radiated interfer-
ences according to Category C2
3)
• Frame sizes FSA to FSC
without integrated line filter with
optional line filter class B
Observance of the limit values
-
for conducted interferences
according to Category C1
-
for field-conducted radiated
interferences according to
Category C2
3)
PM240 Power Modules
• Frame sizes FSD to FSGX
without integrated line filter
2)
• Frame sizes FSD to FSF
with integrated line filter class A
Observance of the limit values
-
according to Category C3
-
for conducted interferences and
field-conducted radiated interfer-
ences according to Category C2
3)
• Frame sizes FSF to FSGX
without integrated line filter with
optional line filter class A
Observance of the limit values
-
according to Category C3
-
for conducted interferences and
field-conducted radiated interfer-
ences according to Category C2
3)
PM250 Power Modules
• Frame size FSC
with integrated line filter class A
Observance of the limit values
according to Category C3 and C2
3)
• Frame size FSC
with integrated line filter class
A and
optional line filter class B
Observance of the limit values
-
for low-frequency harmonic effects
and conducted interferences
according to Category C1
-
for field-conducted radiated interfer-
ences according to Category C2
3)
• Frame sizes FSD to FSF
without integrated line filter
2)
• Frame sizes FSD to FSF
with integrated line filter class A
Observance of the limit values
according to Category C3 and C2
3)
© Siemens AG 2014