SIEMENS
5/14
Siemens D 31 · 2015
5
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
SINAMICS G120 standard inverters
■
Technical specifications
Unless explicitly specified otherwise, the following technical
specifications are valid for all the following components of the
SINAMICS G120 standard inverters.
1)
In product packaging.
2)
In transport packaging.
3)
SIPLUS components for extreme requirements will be available soon.
For further information, please go to
/siplus-drives
General technical specifications
Mechanical specifications
Vibratory load
• Transport in accordance with
EN 60721-3-2
-
Inverters and components,
frame sizes FSA to FSC
1)
Class 1M2
-
Inverters and components,
frame sizes FSD to FSF
2)
Class 2M3
-
Inverters and components,
frame size FSGX
2)
Class 2M2
• Operation acc. to EN 60721-3-3
-
Inverters and components,
frame sizes FSA to FSC
Class 3M1
-
Inverters and components,
frame sizes FSD to FSF
Class 3M1
-
Inverters and components,
frame size FSGX
Test Fc according to EN 60068-2-6
Deflection: 0.075 mm at 10 ... 58 Hz
Acceleration: 10 m/s
2
(1 ×
g
) at
58 ... 200 Hz
Shock load
• Transport in accordance with
EN 60721-3-2
-
Inverters and components,
frame sizes FSA to FSC
1)
Class 1M2
-
Inverters and components,
frame sizes FSD to FSF
2)
Class 2M3
-
Inverters and components,
frame size FSGX
2)
Class 2M2
• Operation acc. to EN 60721-3-3
-
Inverters and components,
frame sizes FSA to FSC
Class 3M2
-
Inverters and components,
frame sizes FSD to FSF
Class 3M1
-
Inverters and components,
frame size FSGX
Test Ea according to EN 60068-2-27
Acceleration: 98 m/s
2
(10 ×
g
) at
20 ms
General technical specifications
Ambient conditions
Protection class
acc. to EN 61800-5-1
Class I (with protective conductor
system) and class III (PELV)
Touch protection
acc. to EN 61800-5-1
For the intended purpose
Permissible ambient and
coolant temperature (air)
during operation for line-side
power components and
Power Modules
• Low overload (LO)
0 ... 40 ºC (32 ... 104 °F)
without derating
>40 ... 60 °C (>104 ... 140 °F)
see derating characteristics
• High overload (HO)
0 ... 50 °C (32 ... 122 °F)
without derating
(for PM240 frame size FSGX:
0 ... 40 °C, 32 ... 104 °F),
>50 ... 60 °C (>104 ... 140 °F)
see derating characteristics
Permissible ambient and
coolant temperature (air)
during operation for Control Units
and supplementary system
components
With CU230P-2 HVAC/DP/CAN:
-10 ... 60 °C (14 ... 140 °F)
With CU230P-2 PN:
-10 ... 55 °C (14 ... 131 °F)
With CU240B-2 and
CU240E-2 (without PN):
-10 ... 55 °C (14 ... 131 °F)
With CU240E-2 PN and
CU240E-2 PN-F:
-10 ... 53 °C (14 ... 127.4 °F)
With CU250S-2:
-10 ... 50 °C (14 ... 122 °F)
With IOP/BOP:
0 ... 50 °C (32 ... 122 °F)
Derating of 3 K/1000 m (3281 ft)
applies to Control Units as of an
installation altitude of 1000 m
(3281 ft) above sea level.
Climatic ambient conditions
• Storage
2)
acc. to EN 60721-3-1
Class 1K3
Temperature -25 ... +55 °C
(-13 ... +131 °F)
• Transport
2)
acc. to EN 60721-3-2
Class 2K4
Temperature -40 ... +70 °C
(-40 ... +158 °F)
Max. air humidity 95% at 40 °C
(104 °F)
• Operation
acc. to EN 60721-3-3
Class 3K3
Condensation, splashwater,
and ice formation not permitted
(EN 60204, Part 1)
Environmental class/harmful
chemical substances
• Storage
2)
acc. to EN 60721-3-1
Class 1C2
• Transport
2)
acc. to EN 60721-3-2
Class 2C2
• Operation
acc. to EN 60721-3-3
Class 3C2
3)
Organic/biological influences
• Storage
2)
acc. to EN 60721-3-1
Class 1B1
• Transport
2)
acc. to EN 60721-3-2
Class 2B1
• Operation
acc. to EN 60721-3-3
Class 3B1
Degree of pollution
acc. to EN 61800-5-1
2
© Siemens AG 2014