9/8
Siemens ST PCS 7 · 2017 (Preliminary edition)
9
■
Technical specifications
(continued)
Compact systems
SIMATIC PCS 7 BOX
Operating system and diagnostics software
Operating system
• SIMATIC PCS 7 BOX RTX
Windows 7 Ultimate SP1 (32-bit), multi-language (English, German, French, Italian, Spanish, Chinese),
pre-installed on hard disk and enclosed on Restore DVD set, no activation required
• SIMATIC PCS 7 BOX
Windows 10 IoT Enterprise 2015 LTSB (64-bit) operating system, multi-language (English, German,
French, Italian, Spanish, Chinese), pre-installed on hard disk and enclosed on Restore DVD set, no acti-
vation required
System-tested SIMATIC industrial software
SIMATIC IPC DiagMonitor
Monitoring and diagnostics functions
Display elements
4 × dual-color LEDs for status display of the operating state:
• PC ON/WD (Watchdog)
• RUN/STOP
• ERROR
• MAINT
SIMATIC IPC DiagMonitor diagnostics software
• Temperature (overtemperature/undertemperature)
• Processor temperature
• Temperature close to the RAM chips
• Temperature of the basic module
• Battery voltage
Backup battery
• Storage media
Monitoring of HDD/SSD with S.M.A.R.T. functionality
• Watchdog
System monitoring; possible reactions: Hardware or software reset
Fans
Monitoring of the fan speed
Operating hours counter
Information about the total runtime
Safety
Protection class
Protection class I according to IEC 61140
Safety directives
EN 60950-1; UL60950-1
CAN/CSA C22.2 No 60950-1-07
UL508
CSA C22.2 No. 142
EN 60950-1
UL508
CSA C22.2 No. 142
Noise emission
Operation
< 55 dB(A) according to EN ISO 7779
Electromagnetic compatibility (EMC)
Interference emission
EN 61000-6-3
EN 61000-6-4
CISPR22 class B
FCC class A
EN 61000-6-3
EN 61000-6-4
CISPR22 class A
FCC class A
Immunity to conducted interference on the supply
lines
±2 kV (according to IEC 61000-4-4; burst)
±1 kV (according to IEC 61000-4-5; symmetrical surge)
±2 kV (according to IEC 61000-4-5; asymmetrical surge)
Immunity to interference on signal lines
±1 kV; (according to IEC 61000-4-4; burst; length < 3 m)
±2 kV; (according to IEC 61000-4-4; burst; length > 3 m)
±2 kV (according to IEC 61000-4-5; surge; length > 30 m)
Immunity to static discharge
±6 kV contact discharge (according to IEC 61000-4-2)
±8 kV air discharge (according to IEC 61000-4-2)
Immunity to radio frequency interference
10 V/m, 80 ... 1 000 MHz and 1.4 ... 2 GHz, 80 % AM (to IEC 61000-4-3)
3 V/m, 2 ... 2.7 GHz, 80 % AM (to IEC 61000-4-3)
10 V/m, 10 kHz ... 80 MHz, 80 % AM (to IEC 61000-4-6)
Immunity to magnetic fields
100 A/m, 50/60 Hz (according to IEC 61000-4-8)
SIMATIC PCS 7 BOX basic hardware:
SIMATIC IPC627D
Standard design
Panel front design
© Siemens AG 2017