Overview
Standard AS 410S automation system
The AS 410S modular standard automation systems are suitable
for general use. These are always your first choice if high avail-
ability through redundancy and safety-related functions are not
relevant for the application.
In the range from 100 to approx. 2 600 POs, their performance
can be customized to meet the task at hand using system ex-
pansion cards (for more information, see the previous section of
the catalog "SD 410 modular systems").
An AS 410S is also the base system for a fault-tolerant
(AS 410H) or a safety-related automation system (AS 410F,
AS 410FH). Your decision for the AS 410S is therefore not final,
you can remain flexible. If the task changes, the automation sys-
tem can be used differently at any time and the target system
can be expanded accordingly.
■
Design
Individual configuration of AS bundles
The configuration of the standard automation systems as well as
the Article No.'s can be defined by selecting pre-configured or-
dering units.
Typical combinations can be selected from the tables in section
"Ordering data" of the paper catalog. The complete range is
available to you via the SIMATIC PCS 7 AS 410 Single Station
online configurator in the Industry Mall.
Subsequent increase in performance
If the performance limit defined by the ordered system expan-
sion card is reached during configuration, commissioning or
operation, a subsequent increase in performance is possible by
using an appropriate number of CPU 410 Expansion Packs
100 POs/500 POs. Hardware modifications are not necessary.
I/O connection via PROFIBUS DP
Several PROFIBUS DP segments with distributed process I/Os
can be operated on one standard automation system. A
PROFIBUS
DP interface is already integrated in the CPU
410-5H
Process Automation. Up to four more PROFIBUS DP interfaces
can be configured via additive CP 443-5 PROFIBUS DP inter-
faces (conformal coating).
I/O connection via PROFINET IO
Standard AS 410S automation systems can only be connected
to remote I/O stations, for example ET 200M/ET 200SP, via
the two PROFINET interfaces (2-port switch) integrated in
CPU 410-5H Process Automation (see also section
"Communication", "PROFINET").
The availability of the I/O devices can be increased by a ring to-
pology with media redundancy (MRP). If the transmission link in
the ring is interrupted at a given location, for example, due to a
break in the ring cable or the failure of a station, the redundancy
manager, e.g. the CPU, immediately activates the alternative
communication path.
Example for PROFINET IO communication with media redundancy
Industrial Ethernet (IE) plant bus communication
If the PROFINET interfaces integrated in the CPU are not used
for PROFINET IO, they can then also be used for the connection
to the Industrial Ethernet plant bus. Otherwise, the AS 410S
standard automation system can be connected to the Industrial
Ethernet plant bus via the CP 443-1 communication module
(conformal coating). If necessary, the availability of plant bus
communication can be increased by using a second CP 443-1
communication module (conformal coating).
Redundant power supply
If you have two separate power supply networks for your plant,
you can increase the availability of the AS 410S standard auto-
mation systems by using two redundant power supplies.
Runtime licenses
The AS bundles come furnished with the SIMATIC PCS 7 Run-
time license for 100 POs. The number of process objects can
be extended by additional Runtime licenses for 100, 1 000 or
10 000 POs. The process objects of additional Runtime licenses
can be added to process objects which already exist. The num-
ber and type (e.g. 100 or 1000) of additional Runtime licenses is
irrelevant with regard to the implementable quantity framework.