SIEMENS
Introduction
General technical data
1/5
Siemens D 86.2 · 2007
1
■
Converter-fed operation
Converters
SINAMICS S converters
The
SINAMICS S120 and S150 converters
allow regenerative
feedback into the supply system. The motor can be operated, if
required, with a rotor position encoder.
SINAMICS G converters
The
SINAMICS G130 and G150 converters
do not allow regen-
erative feedback into the supply system. These converters also
do not support the use of a rotor position encoder. The motor can
only be operated without encoder.
Encoderless speed control
Encoderless speed and torque control has been developed for
the HT-direct motors.
The motors can be started up from a standstill without encoders.
After a few revolutions, the converter can calculate the speed
and position of the rotor from the voltage induced by the mag-
nets in the motor winding. Motor operation down to standstill is
possible. For highly dynamic torque control, an encoder is
required at low speeds. For connection to a rotating machine
(capture) in encoderless operation, a voltage measuring module
is required. This module is offered as an option (K 51) for the
converter and can be used instead of an encoder module.
Synchronized operation of multiple drives
The accuracy for speed or frequency for synchronized operation
of several drives is 0.01% related to the maximum speed or fre-
quency over a period of one second. A SINAMICS converter is
required for each motor.
Approach
Start-up from standstill with full rated torque is possible for
encoderless motors as well as for motors with speed encoders.
Creep operation
Water-jacket-cooled and forced-ventilated motors can be oper-
ated for 3 hours with 1/100 of the rated speed. At this operating
point, the converter is only permitted to be operated at 50% of
the rated current. A speed encoder is required for torque-con-
trolled operation in this range.
In creep mode, if the torque is more than the applicable torque
at 50% of rated current, a converter with a higher rating must be
selected.
Operation in the field weakening range
The field weakening range for the HT-direct motors is limited to
20% of the rated speed. The magnets in the rotor do not allow
conventional field weakening, so field weakening can only be
achieved by the injection of a phase-displaced current by the
converter. In the case of high field-weakening speeds, this
would require an increase in converter frame size. The limited
field-weakening range also ensures that the DC-link voltage of
the converter does not exceed the maximum permissible value
in case of pulse blocking due to the induced voltage of the mo-
tor.
Overload capability
The overload capability of the motor converter system is deter-
mined by the design of the converter and motor (see SINAMICS
catalogs). The motor and converter can be temporarily over-
loaded by up to 50%. The basic load current of the converter that
is available is reduced by overload requirements which may re-
quire selection of a larger converter. For higher overloads and
more complex duty cycles, please submit an enquiry.
Cable lengths between the motor and converter
The maximum cable length for shielded motor connection
cables is 300 m without any additional measures (see the sec-
tion “Bearings and bearing currents”).
Duty type
The standard duty type is S1. For other duty types, please spec-
ify the duty cycle.
Use according to temperature class 130 (previously temperature
class B) available on request.
All converters must be operated at a pulse frequency of
≥
2.5 kHz due to the eddy-current losses that arise in the
magnets.