SIEMENS
3/20
Siemens D 15.1 · 2017
Technical Data
SINAMICS PERFECT HARMONY GH180, article number 6SR4...
3
■
Technical data
(continued)
SINAMICS PERFECT HARMONY GH180
air-cooled drive version
6SR4102-
2.G43-5..0
6SR4102-
2.G44-5..0
6SR4102-
2.H44-5..0
6SR4102-
2.H45-0..0
Motor voltage 6.6 kV
Max. output voltage
kV
6.6
6.6
6.6
6.6
Type rating
kVA
3080
3600
4057
4285
Shaft output
1)
kW
2611
3055
3355
3636
hp
3500
4095
4500
4875
Typical motor current
1)
A
269
315
355
375
Power cell current
A
315
315
375
375
Number of cells
15
15
15
15
Aluminum transformer available
No
No
No
No
Power loss of drive system
• with copper transformer
kW
< 92
< 107
< 118
< 128
• with aluminum transformer
kW
Efficiency
P
out
/
P
in
2)
of drive system
• with copper transformer
%
> 96.5
> 96.5
> 96.5
> 96.5
• with aluminum transformer
%
Auxiliary supply
• Single-phase w/o options
3)
kVA
< 1.5
< 1.5
< 1.5
< 1.5
• Single-phase w/ all options
3)
kVA
< 3
< 3
< 3
< 3
• Three-phase w/o CPT
4)
kVA
< 8
< 8
< 8
< 8
• Three-phase w/ CPT and all
options
4)
kVA
< 11
< 11
< 11
< 11
Cooling medium flow rate
m
3
/s
7.8
7.8
7.8
7.8
CFM
16530
16530
16530
16530
Sound pressure level
L
pA
(1 m)
dB (A)
80
80
80
80
Power cabling cross-sections
• Cable cross-sections,
line-side, max. connectable per
phase
5)
AWG/MCM
(NEC, CEC)
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
mm
2
(DIN VDE)
2 x 240
2 x 240
2 x 240
2 x 240
• Cable cross-sections,
motor-side, max. connectable
per phase
5)
AWG/MCM
(NEC, CEC)
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
mm
2
(DIN VDE)
2 x 240
2 x 240
2 x 240
2 x 240
• PE connection,
max. connection cross-section
at enclosure
5)
AWG/MCM
(NEC, CEC)
2/0 AWG
2/0 AWG
2/0 AWG
2/0 AWG
mm
2
(DIN VDE)
70
70
70
70
Degree of protection
NEMA1/IP21
NEMA1/IP21
NEMA1/IP21
NEMA1/IP21
Drive dimensions (input cabinet, transformer cabinet and cell cabinet)
6)
• Width
mm
4165
4366
4366
4366
in
164
172
172
172
• Height (incl. blowers)
mm
2990
2990
2990
2990
in
117.5
117.5
117.5
117.5
• Depth
mm
1250
1250
1250
1250
in
49
49
49
49
• Schematic drawing
7)
B
B
B
B
Drive weight (input cabinet, transformer cabinet and cell cabinet)
• Weight, approx.
kg
8000
8500
9100
9500
lb
17460
18740
20070
21000
1)
The specifications for the typical motor current and the power data in kW and hp are approximate values only; these have been calculated for operation with
induction motors and for a typical power factor cos
and motor efficiency. Both approximate values have to be adapted to the motor that is actually used.
2)
Values at 100 % of rated speed and torque; includes drive and input transformer.
3)
120/240 V AC for NXGpro control
- CPT is an option.
4)
Includes cooling blowers/pumps; data refers to the largest unit.
5)
Maximum installable size per phase.
6)
If an aluminum transformer is selected, drive dimensions may change.
7)
Please refer to page 3/21
for schematic drawing.