SIEMENS
3/17
Siemens D 15.1 · 2017
Technical Data
SINAMICS PERFECT HARMONY GH180, article number 6SR4...
3
■
Technical data
(continued)
SINAMICS PERFECT HARMONY GH180
air-cooled drive version
6SR4102-
2.B38-0..0
6SR4102-
2.B38-7..0
6SR4102-
2.C38-7..0
6SR4102-
2.C41-0..0
6SR4102-
2.C41-2..0
Motor voltage 6.6 kV
Max. output voltage
kV
6.6
6.6
6.6
6.6
6.6
Type rating
kVA
720
800
810
900
1130
Shaft output
1)
kW
597
662
671
746
933
hp
800
887
900
1000
1250
Typical motor current
1)
A
63
70
71
79
99
Power cell current
A
70
70
100
100
100
Number of cells
15
15
15
15
15
Aluminum transformer available
Yes
Yes
Yes
Yes
Yes
Power loss of drive system
• with copper transformer
kW
< 21
< 24
< 24
< 27
< 33
• with aluminum transformer
kW
< 24
< 27
< 27
< 30
< 38
Efficiency
P
out
/
P
in
2)
of drive system
• with copper transformer
%
96.5
96.5
96.5
96.5
96.5
• with aluminum transformer
%
96
96
96
96
96
Auxiliary supply
• Single-phase w/o options
3)
kVA
< 1.5
< 1.5
< 1.5
< 1.5
< 1.5
• Single-phase w/ all options
3)
kVA
< 3
< 3
< 3
< 3
< 3
• Three-phase w/o CPT
4)
kVA
< 8
< 8
< 8
< 8
< 8
• Three-phase w/ CPT and all
options
4)
kVA
< 11
< 11
< 11
< 11
< 11
Cooling medium flow rate
m
3
/s
4.5
4.5
4.5
4.5
5
CFM
9500
9500
9500
9500
10600
Sound pressure level
L
pA
(1 m)
dB (A)
80
80
80
80
80
Power cabling cross-sections
• Cable cross-sections,
line-side, max. connectable per
phase
5)
AWG/MCM
(NEC, CEC)
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
mm
2
(DIN VDE)
2 x 240
2 x 240
2 x 240
2 x 240
2 x 240
• Cable cross-sections,
motor-side, max. connectable
per phase
5)
AWG/MCM
(NEC, CEC)
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
2 x 500 MCM
mm
2
(DIN VDE)
2 x 240
2 x 240
2 x 240
2 x 240
2 x 240
• PE connection,
max. connection cross-section
at enclosure
5)
AWG/MCM
(NEC, CEC)
2/0 AWG
2/0 AWG
2/0 AWG
2/0 AWG
2/0 AWG
mm
2
(DIN VDE)
70
70
70
70
70
Degree of protection
NEMA1/IP21
NEMA1/IP21
NEMA1/IP21
NEMA1/IP21
NEMA1/IP21
Drive dimensions (transformer cabinet and cell cabinet)
• Width
mm
4165
4165
4165
4165
4165
in
164
164
164
164
164
• Height (incl. blowers)
mm
2990
2990
2990
2990
2990
in
117.5
117.5
117.5
117.5
117.5
• Depth
mm
1250
1250
1250
1250
1250
in
49
49
49
49
49
• Schematic drawing
6)
B
B
B
B
B
Drive weight (transformer cabinet and cell cabinet)
• Weight, approx.
kg
5300
5400
5400
5500
5700
lb
11680
11900
11900
12130
12570
1)
The specifications for the typical motor current and the power data in kW and hp are approximate values only; these have been calculated for operation with
induction motors and for a typical power factor cos
and motor efficiency. Both approximate values have to be adapted to the motor that is actually used.
2)
Values at 100 % of rated speed and torque; includes drive and input transformer.
3)
120/240 V AC for NXGpro control
- 6SR4... drives derive single-phase control power from a built-in CPT as standard.
- For 6SR4... drives, customers can directly connect single-phase control power as an option (
K68
).
- CPT is an option in other systems.
4)
Includes cooling blowers/pumps; data refers to the largest unit.
5)
Maximum installable size per phase.
6)
Please refer to page 3/3
for schematic drawings.
© Siemens AG 2017