SIEMENS
2/12
Siemens D 15.1 · 2017
SINAMICS PERFECT HARMONY GH180
Air-Cooled Drives
Selection and ordering data
2
■
Selection and ordering data
(continued)
Motor voltage 6.6 kV
Note:
The drive types in the color-coded rows of the table can be ordered with a significantly shorter delivery time with option
B19
(Express
Line).
Motor voltage
Type rating
Shaft output
1)
Shaft output
1)
Typical motor
current
1)
Power cell
current
Number of
cells
Article No.
kV
kVA
kW
hp
A
A
6.6
270
224
300
24
40
15
6SR4102-2
■
A33-0
■
■
0
6.6
360
298
400
32
40
15
6SR4102-2
■
A34-0
■
■
0
6.6
450
373
500
39
40
15
6SR4102-2
■
A35-0
■
■
0
6.6
455
378
507
40
40
15
6SR4102-2
■
A36-0
■
■
0
6.6
540
448
600
47
70
15
6SR4102-2
■
B36-0
■
■
0
6.6
630
522
700
55
70
15
6SR4102-2
■
B37-0
■
■
0
6.6
720
597
800
63
70
15
6SR4102-2
■
B38-0
■
■
0
6.6
800
662
887
70
70
15
6SR4102-2
■
B38-7
■
■
0
6.6
810
671
900
71
100
15
6SR4102-2
■
C38-7
■
■
0
6.6
900
746
1000
79
100
15
6SR4102-2
■
C41-0
■
■
0
6.6
1130
933
1250
99
100
15
6SR4102-2
■
C41-2
■
■
0
6.6
1140
946
1268
100
100
15
6SR4102-2
■
C41-5
■
■
0
6.6
1350
1119
1500
118
140
15
6SR4102-2
■
D41-5
■
■
0
6.6
1580
1306
1750
138
140
15
6SR4102-2
■
D41-7
■
■
0
6.6
1600
1324
1775
140
140
15
6SR4102-2
■
D42-0
■
■
0
6.6
1760
1492
2000
154
200
15
6SR4102-2
■
E42-0
■
■
0
6.6
1980
1679
2250
173
200
15
6SR4102-2
■
E42-2
■
■
0
6.6
2200
1865
2500
192
200
15
6SR4102-2
■
E42-5
■
■
0
6.6
2285
1939
2600
200
200
15
6SR4102-2
■
E43-0
■
■
0
6.6
2640
2238
3000
231
260
15
6SR4102-2
■
F43-0
■
■
0
6.6
2970
2521
3380
260
260
15
6SR4102-2
■
F43-5
■
■
0
6.6
3080
2611
3500
269
315
15
6SR4102-2
■
G43-5
■
■
0
6.6
3600
3055
4095
315
315
15
6SR4102-2
■
G44-5
■
■
0
6.6
4057
3355
4500
355
375
15
6SR4102-2
■
H44-5
■
■
0
6.6
4285
3636
4875
375
375
15
6SR4102-2
■
H45-0
■
■
0
6.6
4400
3730
5000
385
500
18
6SR3102-7
■
J45-0
■
■
0
6.6
5280
4476
6000
462
500
18
6SR3102-7
■
J46-0
■
■
0
6.6
5715
4849
6500
500
500
18
6SR3102-7
■
J47-0
■
■
0
6.6
6160
5222
7000
539
660
18
6SR3102-7
■
K47-0
■
■
0
6.6
7040
5968
8000
615
660
18
6SR3102-7
■
K48-0
■
■
0
For article No. key, see page 2/13
1)
The specifications for the typical motor current and the power data in kW and hp are approximate values only; these have been calculated for operation with
induction motors and for a typical power factor cos
and motor efficiency. Both approximate values have to be adapted to the motor that is actually used.
© Siemens AG 2017