SIEMENS
2/9
Siemens D 15.1 · 2017
SINAMICS PERFECT HARMONY GH180
Air-Cooled Drives
Selection and ordering data
2
■
Selection and ordering data
(continued)
Motor voltage 4.0/4.16 kV
Motor voltage
Type rating
Shaft output
1)
Shaft output
1)
Typical motor
current
1)
Power cell
current
Number of
cells
Article No.
kV
kVA
kW
hp
A
A
4.0/4.16
2)
180
149
200
26
40
9
6SR4102-0
■
A32-0
■
■
0
4.0/4.16
2)
270
224
300
39
40
9
6SR4102-0
■
A33-0
■
■
0
4.0/4.16
2)
275
229
307
40
40
9
6SR4102-0
■
A34-0
■
■
0
4.0/4.16
2)
360
298
400
52
70
9
6SR4102-0
■
B34-0
■
■
0
4.0/4.16
2)
410
336
450
59
70
9
6SR4102-0
■
B34-5
■
■
0
4.0/4.16
2)
450
373
500
65
70
9
6SR4102-0
■
B35-0
■
■
0
4.0/4.16
2)
480
401
538
70
70
9
6SR4102-0
■
B36-0
■
■
0
4.0/4.16
2)
540
448
600
78
100
9
6SR4102-0
■
C36-0
■
■
0
4.0/4.16
2)
630
522
700
91
100
9
6SR4102-0
■
C37-0
■
■
0
4.0/4.16
2)
690
573
768
100
100
9
6SR4102-0
■
C38-0
■
■
0
4.0/4.16
2)
720
597
800
104
140
9
6SR4102-0
■
D38-0
■
■
0
4.0/4.16
2)
810
671
900
117
140
9
6SR4102-0
■
D38-7
■
■
0
4.0/4.16
2)
900
746
1000
130
140
9
6SR4102-0
■
D41-0
■
■
0
4.0/4.16
2)
965
802
1075
140
140
9
6SR4102-0
■
D41-1
■
■
0
4.16
3080
2611
3500
427
500
12
6SR3102-3
■
J43-5
■
■
0
4.16
3520
2984
4000
488
500
12
6SR3102-3
■
J44-0
■
■
0
4.16
3600
3056
4097
500
500
12
6SR3102-3
■
J45-0
■
■
0
4.16
4400
3730
5000
610
660
12
6SR3102-3
■
K45-0
■
■
0
4.16
4540
3851
5162
630
660
12
6SR3102-3
■
K46-0
■
■
0
For article No. key, see page 2/13
1)
The specifications for the typical motor current and the power data in kW and hp are approximate values only; these have been calculated for operation with
induction motors and for a typical power factor cos
and motor efficiency. Both approximate values have to be adapted to the motor that is actually used.
2)
4.16 kV possible with overmodulation; under load, motor operates with 4.0 kV.
© Siemens AG 2017