SIEMENS
5/64
Siemens D 31 · 2015
5
■
Technical specifications
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Power Modules
1)
The rated output current
I
rated
and the base-load current
I
L
are based on
the duty cycle for low overload (LO).
2)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
3)
Typical values. You can find more information on the Internet at
4)
The input current depends on the motor load and line impedance. The
input currents apply for a load at rated power (based on
I
rated
) for a line
impedance corresponding to
u
K
= 1 %. These current values without line
reactor are specified on the rating plate of the Power Module.
5)
Max. motor cable length 25 m (shielded) for PM240 Power Modules with
integrated line filter to maintain the limit values according to EN 61800-3
Category C2.
Line voltage 380 ... 480 V 3 AC
PM240 Power Modules
Without integrated line filter
6SL3224-
0BE34-5UA0
6SL3224-
0BE35-5UA0
6SL3224-
0BE37-5UA0
6SL3224-
0BE38-8UA0
6SL3224-
0BE41-1UA0
With integrated line filter
6SL3224-
0BE34-5AA0
6SL3224-
0BE35-5AA0
6SL3224-
0BE37-5AA0
–
–
Output current
at 50 Hz 400 V 3 AC
• Rated current
I
rated
1)
A
110
145
178
205
250
• Base-load current
I
L
1)
A
110
145
178
205
250
• Base-load current
I
H
2)
A
90
110
145
178
205
• Maximum current
I
max
A
180
220
290
308
375
Rated power
• Based on
I
L
kW (hp)
55 (75)
75 (100)
90 (125)
110 (150)
132 (200)
• Based on
I
H
kW (hp)
45 (60)
55 (75)
75 (100)
90 (125)
110 (150)
Rated pulse frequency
kHz
4
4
4
2
2
Efficiency
η
>0.97
>0.97
>0.97
>0.97
>0.97
Power loss
3)
At rated current
kW
1.484
2.079
2.376
2.274
2.964
Cooling air requirement
m
3
/s
0.15
0.15
0.15
0.15
0.15
Sound pressure level
L
pA
(1 m)
dB
<60
<60
<65
<65
<65
24 V DC power supply
for Control Unit
A
1
1
1
1
1
Rated input current
4)
• With line reactor
A
115
151
186
210
250
• Without line reactor
A
129
168
204
245 (9.65)
299
Length of cable to braking
resistor, max.
m (ft)
15 (49)
15 (49)
15 (49)
15 (49)
15 (49)
Line supply connection
U1/L1, V1/L2, W1/L3
M8 screw stud
M8 screw stud
M8 screw stud
M8 screw stud
M8 screw stud
• Conductor cross-section
mm
2
25 ... 120
25 ... 120
25 ... 120
25 ... 120
25 ... 120
Motor connection
U2, V2, W2
M8 screw stud
M8 screw stud
M8 screw stud
M8 screw stud
M8 screw stud
• Conductor cross-section
mm
2
25 ... 120
25 ... 120
25 ... 120
25 ... 120
25 ... 120
DC link connection,
connection for braking resistor
DCP/R1, DCN, R2
M8 screw stud
M8 screw stud
M8 screw stud
M8 screw stud
M8 screw stud
• Conductor cross-section
mm
2
25 ... 120
25 ... 120
25 ... 120
25 ... 120
25 ... 120
PE connection
On housing with
M8 screw
On housing with
M8 screw
On housing with
M8 screw
On housing with
M8 screw
On housing with
M8 screw
Motor cable length
5)
, max.
• Shielded
m (ft)
50 (164)
50 (164)
50 (164)
50 (164)
50 (164)
• Unshielded
m (ft)
100 (328)
100 (328)
100 (328)
100 (328)
100 (328)
Degree of protection
IP20
IP20
IP20
IP20
IP20
Dimensions
• Width
mm (in)
350 (13.78)
350 (13.78)
350 (13.78)
350 (13.78)
350 (13.78)
• Height
-
Without integrated line filter
mm (in)
634 (24.96)
634 (24.96)
634 (24.96)
634 (24.96)
634 (24.96)
-
With integrated line filter
mm (in)
934 (36.77)
934 (36.77)
934 (36.77)
–
–
• Depth
-
Without operator panel
mm (in)
316 (12.44)
316 (12.44)
316 (12.44)
316 (12.44)
316 (12.44)
-
With operator panel, max.
mm (in)
390 (15.35)
390 (15.35)
390 (15.35)
390 (15.35)
390 (15.35)
Frame size
FSF
FSF
FSF
FSF
FSF
Weight, approx.
• Without integrated line filter
kg (lb)
36 (79.4)
36 (79.4)
36 (79.4)
39 (86)
39 (86)
• With integrated line filter
kg (lb)
52 (115)
52 (115)
52 (115)
–
–
© Siemens AG 2014