Technical specifications
SINAMICS G110 standard inverters
0.12 kW to 3 kW (0.16 hp to 4 hp)
Controlled Power Modules
1)
Applies to industrial control panel installations to NEC article 409 or UL 508A.
Controlled Power Modules
Power range
0.12 ... 3 kW (0.16 ... 4 hp)
Line voltage
200 ... 240 V ±10 % 1 AC
Line frequency
47 ... 63 Hz
Output frequency
0 ... 650 Hz (a 550 Hz limit is in preparation in order to satisfy legal requirements)
Output voltage
200 ... 240 V 3 AC
Offset factor cos
ϕ
≥
0.95
Inverter efficiency
• For devices < 0.75 kW
90 ... 94 %
• For devices
≥
0.75 kW
≥
95 %
Overload capability
Overload current 1.5 × rated output current (i.e. 150 % overload) for 60 s,
then 0.85 × rated output current for 240 s,
cycle time 300 s
Inrush current
Not higher than the rated input current
Control methods
Linear V/f characteristic (with parameterizable voltage boost);
square V/f characteristic;
multipoint characteristic (parameterizable V/f characteristic)
Pulse frequency
8 kHz (standard)
2 ... 16 kHz (in 2 kHz increments)
Fixed frequencies
3, programmable
Skippable frequency range
1, programmable
Setpoint resolution
0.01 Hz digital
0.01 Hz serial
10 bit analog (motorized potentiometer 0.1 Hz)
Digital inputs
3 programmable digital inputs, non-floating; PNP type, SIMATIC-compatible
Analog input (analog variant)
1, for setpoint (0 ... 10 V, scaleable or for use as 4th digital input)
Digital output
1 isolated optocoupler output (24 V DC, 50 mA, ohmic, NPN type)
Universal serial interface (USS variant)
RS485, for operation with USS protocol
Motor cable length, max.
• Shielded
25 m (82 ft)
• Unshielded
50 m (164 ft)
Electromagnetic compatibility
All devices with integrated EMC filter for drive systems in
category C2 installations (limit value in accordance with EN 55011, class A, group 1) and
category C3 installations (limit value in accordance with EN 55011, class A, group 2).
All devices with an integrated EMC filter and shielded cables with a maximum length of 5 m (16 ft) also fulfill the
limit values of EN 55011, class B for conducted interference.
Braking
DC injection braking, compound braking
Degree of protection
IP20
Operating temperature
-10 … +40 °C (14 °F ... 104 °F)
up to +50°C (122 °F) with derating
Storage temperature
-40 ... +70 °C (-40 °F ... +158 °F)
Relative humidity
95 % (non-condensing)
Installation altitude
Up to 1000 m (3281 ft) above sea level without derating
• Rated output current
at 4000 m (13124 ft) above sea level: 90 %
• Line voltage
up to 2000 m (6562 ft) above sea level: 100 %
at 4000 m (13124 ft) above sea level: 75 %
SCCR (S
hort C
ircuit C
urrent R
ating)
according to UL
1)
10 kA (up to maximum 100 kA)
Protection features for
• Undervoltage
• Overvoltage
• Ground fault
• Short-circuit
• Stall protection
• Thermal motor protection
I
2
t
• Inverter overtemperature
• Motor overtemperature
Compliance with standards
UL, cUL, CE, C-Tick
CE marking, according to
Low-Voltage Directive 2006/95/EC
© Siemens AG 2014