SIEMENS
5/45
Siemens D 31 · 2015
5
■
Integration
SINAMICS G120 standard inverters
0.37 kW to 250 kW (0.5 hp to 400 hp)
Power Modules
Derating data
The following inverter output currents can still be achieved with
long motor cables without output reactor and sine-wave filter.
Derating for PM240 Power Modules, frame sizes FSD to FSF,
for shielded motor cables. Tested were carried out only on the
particular main Power Module types. The values also apply to
the other Power Modules of the particular frame size.
–
Not possible
1)
Additional information is available on the Internet at
/sinamics-g120/documentation
2)
Rated power based on the rated output current
I
rated
. The rated output
current
I
rated
is based on the duty cycle for low overload (LO).
3)
The rated output current
I
rated
is based on the duty cycle for low overload
(LO). These current values are valid for 400 V and are specified on the
rating plate of the Power Module.
Maximum permissible motor cable lengths (shielded/unshielded) in m
Frame size
FSA
FSB
FSC
FSD
FSE
FSF
FSGX
PM240-2 Power Module with integrated braking chopper
(continued)
With optional external line filter
class B (EMC category C1
1)
,
with unfiltered Power Module,
maintains the limit values
acc. to EN 61800-3)
• At 380 ... 415 V 3 AC
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
–
–
–
–
• At 440 ... 480 V 3 AC
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
–
–
–
–
With optional external line filter
class B and output reactor
(EMC category C2
1)
, with
unfiltered Power Module,
maintains the limit values
acc. to EN 61800-3)
• At 380 ... 415 V 3 AC
150/–
(492/–)
150/–
(492/–)
150/–
(492/–)
–
–
–
–
• At 440 ... 480 V 3 AC
100/–
(328/–)
100/–
(328/–)
100/–
(328/–)
–
–
–
–
PM240 Power Module with integrated braking chopper
Without
integrated
braking chopper
Available frame sizes
–
–
–
Without output reactor/
sine-wave filter
–
–
–
50/100
(164/328)
50/100
(164/328)
50/100
(164/328)
200/300
(656/984)
With optional output reactor
• At 380 -10 % ... 400 V 3 AC
–
–
–
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
300/450
(984/1476)
• At 401 ... 480 V 3 AC +10 %
–
–
–
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
300/450
(984/1476)
With optional sine-wave filter
• At 380 -10 % ... 400 V 3 AC
–
–
–
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
300/450
(984/1476)
• At 401 ... 480 V 3 AC +10 %
–
–
–
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
300/450
(984/1476)
PM250 Power Module with line-commutated energy recovery
Available frame sizes
–
–
–
Without output reactor/
sine-wave filter
–
–
50/100
(164/328)
50/100
(164/328)
50/100
(164/328)
50/100
(164/328)
–
With optional output reactor
• At 380 -10 % ... 400 V 3 AC
–
–
150/225
(492/738)
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
–
• At 401 ... 480 V 3 AC +10 %
–
–
100/150
(328/492)
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
–
With optional sine-wave filter
• At 380 -10 % ... 400 V 3 AC
–
–
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
–
• At 401 ... 480 V 3 AC +10 %
–
–
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
–
Rated power
1)
Frame size
Rated output
current
I
rated
2)
Base-load
current
I
H
Motor
connection
cross-section
Current derating
of the output current as a % of the base-load current for the
cable lengths (MOTION-CONNECT)
kW
hp
A
A
mm
2
50 m
100 m
150 m
200 m
30
40
FSD
60
45
35
100 %
95 %
90 %
85 %
45
60
FSE
90
75
35
100 %
100 %
95 %
90 %
90
125
FSF
178
145
95
100 %
100 %
100 %
95 %
© Siemens AG 2014