SIEMENS
2/27
Siemens PM 21 · 2017
SIMOTION Motion Control System
SIMOTION D – Drive-based
SIMOTION D4x5-2 Control Units
2
■
Technical specifications
(continued)
Article number
6AG1435-2AD00-4AA0
6AG1455-2AD00-4AA0
Product brand name
SIPLUS
SIPLUS
Product type designation
D435-2 DP/PN SIPLUS
D455-2 DP/PN SIPLUS
General technical specifications
(continued)
Ambient temperature during
• Long-term storage
°C (°F)
-25 ... +55 (-13 ... +131)
-25 ... +55 (-13 ... +131)
• Transport
°C (°F)
-40 ... +70 (-40 ... +158)
-40 ... +70 (-40 ... +158)
• Operation
°C (°F)
0 ... 55 (32 ... 131)
0 ... 55 (32 ... 131)
- Note
Maximum installation altitude 4000 m (13124 ft)
above sea level. Above an altitude of 2000 m
(6562 ft), the max. ambient temperature decreases
by 7 °C (44.6 °F) every 1000 m (3281 ft).
Maximum installation altitude 4000 m (13124 ft)
above sea level. Above an altitude of 2000 m
(6562 ft), the max. ambient temperature decreases
by 7 °C (44.6 °F) every 1000 m (3281 ft).
Relative humidity
• during operation
%
0 ... 100
0 ... 100
• with condensation, tested acc. to
IEC 60068-2-38
Condensation/frost permitted
(no commissioning when condensation is present)
Condensation/frost permitted
(no commissioning when condensation is present)
Conformal coating
Yes
Yes
Resistance
• to biologically active substances,
conformity according to
EN 60721-3-3
Yes
Yes
- Note
Class 3B2 mold and fungal spores (except fauna);
the supplied plug covers must be left on the unused
interfaces during operation!
Class 3B2 mold and fungal spores (except fauna);
the supplied plug covers must be left on the unused
interfaces during operation!
• to chemically active substances,
conformity according to
EN 60721-3-3
Yes
Yes
- Note
Class 3C4 incl. salt spray according to
EN 60068-2-52 (severity 3); the plug covers included
in delivery must be left on the unused interfaces
during operation!
Class 3C4 incl. salt spray according to
EN 60068-2-52 (severity 3); the plug covers included
in delivery must be left on the unused interfaces
during operation!
Atmospheric pressure
hPa
620 ... 1 060
620 ... 1 060
Degree of protection
IP20
IP20
Height
mm (in)
380 (15.0)
380 (15.0)
Width
mm (in)
50 (1.97)
50 (1.97)
Depth
mm (in)
270 (10.6)
270 (10.6)
• Note
With disassembled spacer 230 mm (9.05 in) depth
With disassembled spacer 230 mm (9.05 in) depth
Net weight
g (lb)
3 700 (8.1571)
4 300 (9.47988)
Digital inputs
Number of digital inputs
12
12
DC input voltage
• Rated value
V
24
24
• For signal "1"
V
15 ... 30
15 ... 30
• For signal "0"
V
-3 ... +5
-3 ... +5
Galvanic isolation
Yes
Yes
• Note
In groups of 6
In groups of 6
Current consumption at signal level
"1", typ.
mA
9
9
Input delay time for
• Signal "0"
"1", typ.
μs
50
50
• Signal "1"
"0", typ.
μs
150
150
Digital inputs/outputs
Number of digital inputs/
outputs
16
16
Parameter assignment options
for digital inputs and outputs
Parameterizable as DI, as DO, as measuring input
(max. 16), as cam output (max. 8)
Parameterizable as DI, as DO, as measuring input
(max. 16), as cam output (max. 8)
© Siemens AG 2017