SIEMENS
2/4
Siemens D 84.9 · 2015
2
Motors for operation on line or with SINAMICS PERFECT HARMONY converters
Open-circuit cooled motors
SIMOTICS HV Series A-compact PLUS 1RA1, 1RP1
■
Selection and ordering data
(continued)
Note:
For frame size 315, only 1RA1, 2-poles, 6 kV / 6.6 kV design is available.
Efficiencies according to IEC 60034-2-1.
Rated
power
High voltage motor
A-compact PLUS
Speed
Rated
current
Efficiency
Power factor
Torque
Break-
down
torque
Locked-
rotor
torque
Locked-
rotor
current
Cool-
ing air
flow
rate
Moment of
inertia
P
rated
130 (B)
1)
I
rated
at
6 kV
4/4
load
3/4
load
4/4
load
3/4
load
T
rated
T
B
/
T
rated
T
LR
/
T
rated
I
LR
/
I
rated
Motor
Exter-
nal,
max.
kW
Article number
rpm
A
%
%
cos
ϕ
cos
ϕ
Nm
[-]
[-]
[-]
m
3
/s
kgm
2
kgm
2
6 kV, 50 Hz
4-pole
500
1RA1350-4HA6
7
1479
59
94.5
94.6
0.87
0.83
3229
2.4
0.90
5.2
1.0
6.8
220
560
1RA1352-4HA6
7
1477
65
94.6
94.9
0.87
0.86
3620
2.4
0.90
5.2
1.0
7.5
265
630
1RA1354-4HA6
7
1479
73
94.9
95.1
0.87
0.86
4069
2.4
0.90
5.3
1.0
8.2
290
710
1RA1356-4HA6
7
1479
82
95.1
95.3
0.88
0.86
4584
2.5
1.10
5.6
1.0
9.1
305
800
1RA1400-4HA6
7
1482
93
95.1
95.2
0.87
0.85
5155
2.4
0.90
5.5
1.5
12.9
265
900
1RA1402-4HA6
7
1482
104
95.2
95.4
0.88
0.86
5799
2.4
0.90
5.5
1.5
13.9
285
1000
1RA1404-4HA6
7
1482
114
95.4
95.6
0.89
0.88
6444
2.4
0.90
5.5
1.5
15.6
320
1120
1RA1406-4HA6
7
1484
126
95.5
95.7
0.89
0.87
7209
2.6
1.10
6.2
1.5
17.4
335
1250
1RA1450-4HA6
7
1484
142
95.5
95.7
0.88
0.86
8044
2.9
0.90
6.2
2.0
19.0
330
1400
1RA1450-4HB6
7
1480
160
95.4
95.7
0.88
0.87
9034
2.4
0.90
5.5
2.0
19.0
240
1600
1RA1452-4HA6
7
1479
182
95.5
95.9
0.88
0.88
10331
2.4
0.80
5.5
2.0
21.0
265
1800
1RA1454-4HA6
7
1481
205
95.8
96.0
0.88
0.87
11607
2.7
0.90
5.8
2.0
23.0
265
2000
1RA1456-4HA6
7
1481
225
95.9
96.2
0.89
0.88
12897
2.7
0.90
5.8
2.0
25.0
290
2240
1RA1500-4HA6
7
1483
250
95.7
96.0
0.89
0.87
14422
2.5
0.85
5.1
2.8
38.8
180
2500
1RA1502-4HA6
7
1485
280
95.8
96.1
0.89
0.87
16082
2.6
0.90
5.5
2.8
42.9
200
2800
1RA1504-4HA6
7
1485
315
95.9
96.3
0.89
0.87
18008
2.6
0.90
5.5
2.8
47.2
220
3150
1RA1506-4HA6
7
1486
355
96.2
96.5
0.89
0.87
20240
2.8
1.00
5.7
2.8
52.4
250
3550
1RA1560-4HJ6
7
1489
400
96.7
96.8
0.88
0.85
22764
2.5
0.60
5.8
3.1
84.3
1400
4000
1RA1562-4HJ6
7
1489
450
96.8
97.0
0.88
0.85
25653
2.5
0.60
5.8
3.1
89.8
1400
4700
1RA1564-4HJ6
7
1488
530
96.9
97.1
0.88
0.85
30163
2.5
0.60
5.8
3.1
94.6
1400
4950
1RA1566-4HJ6
7
1487
560
96.9
97.1
0.88
0.86
31782
2.5
0.60
5.8
3.1
96.7
1400
5000
1RA1630-4HJ6
7
1490
560
97.1
97.0
0.88
0.87
32056
3.0
0.60
6.0
3.7
131.3
1450
5500
1RA1630-4HK6
7
1489
620
97.1
97.0
0.88
0.85
35266
2.9
0.60
6.0
3.7
131.3
1300
5600
1RA1632-4HJ6
7
1490
630
97.1
97.1
0.88
0.86
35902
2.9
0.60
6.0
3.7
142.9
1350
6600
1RA1634-4HJ6
7
1489
740
97.2
97.2
0.88
0.86
42333
2.9
0.60
6.0
3.7
154.2
1350
7100
1RA1636-4HJ6
7
1489
800
97.2
97.2
0.88
0.86
45537
2.9
0.60
6.0
3.7
168.3
1400
Type of construction
7
See page 1/9
1)
Thermal class 155 (F), utilized to 130 (B).
© Siemens AG 2015