ABB
ABB/ BU Machines / HV Induction motors IEC catalogue / Engineered motors EN 12-2007
95
2
Efficiency
Power factor
Current
Torque
Sound
Full
3/4
Full
3/4
I
N
I
S
I
0
T
N
T
S
T
max
Rotor
Motor
pressure
Output
Motor
Product
Speed
load
load
load
load
inertia
weight
level L
P
kW
type
ID
r/min
100%
75%
100% 75%
A
I
N
A
Nm
T
N
T
N
kgm
2
kg
dB(A)
HV Modular motors
Technical data for open weather protected
three phase motors
IP 24W - IC 01 - Insulation class F, temperature rise class B
10000 V - 50 Hz
1000 r/min = 6 poles
10000 V 50 Hz
500
AMA 450L6W
8643
991
95.4
95.3
0.83
0.78
37
6.0
15
4816
0.9
2.4
28.4
3870
78
560
AMA 450L6W
8644
990
95.4
95.4
0.84
0.80
40
5.4
15
5401
0.8
2.2
28.4
3870
78
630
AMA 450L6W
8645
989
95.3
95.5
0.85
0.82
45
5.0
15
6084
0.8
2.0
28.5
3870
78
710
AMA 450L6W
8646
990
95.6
95.7
0.84
0.81
51
5.4
18
6852
0.8
2.1
30.1
3990
78
800
AMA 450L6W
8647
989
95.5
95.8
0.85
0.83
57
4.8
18
7726
0.7
1.9
30.3
4000
78
900
AMA 450L6W
8648
989
95.5
95.8
0.85
0.82
64
4.8
21
8690
0.7
1.9
30.4
4000
78
1000
AMA 500L6W
181
994
95.9
96.1
0.87
0.85
69
5.6
21
9610
0.6
2.1
61.7
4970
79
1120
AMA 500L6W
182
994
96.0
96.3
0.87
0.85
77
5.6
24
10763
0.6
2.1
65.2
5120
79
1250
AMA 500L6W
183
993
96.1
96.3
0.87
0.85
86
5.6
27
12018
0.7
2.1
68.1
5260
79
1400
AMA 500L6W
488
993
96.2
96.5
0.87
0.85
96
5.6
30
13460
0.7
2.1
71.8
5420
79
1600
AMA 500L6W
489
992
96.1
96.5
0.88
0.87
109
5.5
30
15397
0.7
2.0
72.8
5430
79
750 r/min = 8 poles
10000 V 50 Hz
710
AMA 500L8W
8649
744
95.5
95.7
0.84
0.81
51
5.8
19
9107
0.8
2.1
71.8
4930
77
800
AMA 500L8W
185
745
95.7
95.9
0.84
0.80
58
5.6
22
10255
0.7
2.1
76.3
5080
77
900
AMA 500L8W
186
745
95.9
96.0
0.84
0.80
65
5.5
25
11538
0.7
2.0
80.8
5230
77
1000
AMA 500L8W
187
745
95.9
96.1
0.83
0.79
72
5.6
28
12819
0.8
2.1
85.2
5380
77
1120
AMA 500L8W
490
745
96.1
96.3
0.84
0.81
80
5.5
30
14359
0.7
2.0
94.1
5670
77
1250
AMA 500L8W
491
744
96.0
96.3
0.86
0.83
88
5.5
29
16039
0.8
2.0
94.8
5680
77
600 r/min = 10 poles
10000 V 50 Hz
500
AMA 500L10W
188
594
94.4
94.6
0.82
0.78
37
5.5
16
8034
0.9
2.2
67.4
4750
77
560
AMA 500L10W
189
594
94.6
94.8
0.83
0.79
41
5.4
17
9002
0.8
2.1
71.9
4900
77
630
AMA 500L10W
190
594
94.7
95.0
0.84
0.80
46
5.2
18
10130
0.8
2.1
76.3
5050
77
710
AMA 500L10W
191
595
94.9
95.2
0.83
0.79
52
5.3
21
11404
0.8
2.1
81.6
5200
77
800
AMA 500L10W
492
595
95.0
95.3
0.83
0.79
58
5.3
24
12849
0.8
2.1
86.1
5350
77
500 r/min = 12 poles
10000 V 50 Hz
355
AMA 500L12W
8659
494
93.3
93.5
0.76
0.70
29
4.1
15
6859
0.6
1.9
54.3
4610
77
400
AMA 500L12W
8660
494
93.6
93.7
0.75
0.69
33
4.2
17
7725
0.6
2.0
58.0
4760
77
450
AMA 500L12W
8661
495
94.0
94.0
0.76
0.70
37
4.3
18
8690
0.6
2.0
65.4
5050
77
500
AMA 500L12W
195
495
94.0
94.1
0.78
0.72
39
4.9
19
9654
0.7
2.1
80.8
5180
77
560
AMA 500L12W
196
494
94.1
94.3
0.78
0.73
44
4.8
21
10815
0.7
2.0
85.3
5330
77
630
AMA 500L12W
495
494
94.3
94.4
0.78
0.73
49
4.7
24
12169
0.7
2.0
89.7
5470
77
Data presented in rating lists are typical values.
Guaranteed values on request. All engineered motors
are optimized for the specified application. Accurate
motor data will be given on request at quotation phase.
Legally binding performance and specification data is
given to the end user once each order is confirmed.